An Approach to Performing Stability Analysis for Power Transformer Differential Protection: A Case Study

Author

Listed:
  • Muhammad Sheryar

    (Department of Electrical Testing and Commissioning, Mansour Al Mosaid Group, Jeddah 22312, Saudi Arabia)

  • Muhammad Ahsan Ali

    (Department of Electrical Testing and Commissioning, Mansour Al Mosaid Group, Jeddah 22312, Saudi Arabia)

  • Farhana Umer

    (Department of Electrical Engineering, The Islamia University of Bahawalpur, Bahawalpur 63100, Pakistan)

  • Zeeshan Rashid

    (Department of Electrical Engineering, The Islamia University of Bahawalpur, Bahawalpur 63100, Pakistan)

  • Muhammad Amjad

    (Department of Electronics Engineering, The Islamia University of Bahawalpur, Bahawalpur 63100, Pakistan)

  • Zunaib Maqsood Haider

    (Department of Electrical Engineering, The Islamia University of Bahawalpur, Bahawalpur 63100, Pakistan)

  • Muhammad Omer Khan

    (Department of Electrical Engineering & Technology, Riphah International University, Faisalabad 37000, Pakistan)

Abstract

Differential protection normally detects short circuits and ground faults in the windings of a power transformer and its terminals. Inter-turn faults refer to flashovers among the electrodes that arise only in a similar type of physical winding. Inter-turn faults can be examined when the adequate sum of turns is served as short-circuited. In electrical protection, it is difficult to detect inter-turn faults. An inter-turn fault of small magnitude is based on the limited number of turns that resultantly provide a large quantity of current. Due to this reason, protection that comes from the differential scenario possesses a higher degree of sensitivity without causing unwanted operations during external faults. In this paper, a protection-based stability method is proposed whereby external voltages are applied at the low-voltage (LV) side of the transformer while keeping the high-voltage (HV) side short-circuited. This was conducted using a three-phase power transformer (rating: 100 MVA, 380 kV/13.8 kV) at SWCC Shoaiba Power Plant, Saudi Arabia. In this work, differential protection (87T) and high-impedance differential protection for HV-restricted earth faults (REFs) were verified by creating In-Zone and Out-Zone fault conditions to ensure current transformer (CT) circuits and tripping logic. All of the IEDs, protection, and control schemes involved were designed by ABB. This method verifies protection stability for power transformers by implementing differential protection (87T) and high-impedance restricted earth fault (64HV) schemes through creating In-Zone and Out-Zone fault conditions.

Suggested Citation

  • Muhammad Sheryar & Muhammad Ahsan Ali & Farhana Umer & Zeeshan Rashid & Muhammad Amjad & Zunaib Maqsood Haider & Muhammad Omer Khan, 2022. "An Approach to Performing Stability Analysis for Power Transformer Differential Protection: A Case Study," Energies, MDPI, vol. 15(24), pages 1-16, December.
  • Handle: RePEc:gam:jeners:v:15:y:2022:i:24:p:9603-:d:1007012
    as

    Download full text from publisher

    File URL: https://www.mdpi.com/1996-1073/15/24/9603/pdf
    Download Restriction: no

    File URL: https://www.mdpi.com/1996-1073/15/24/9603/
    Download Restriction: no
    ---><---

    References listed on IDEAS

    as
    1. Umer Ehsan & Muhammad Jawad & Umar Javed & Khurram Shabih Zaidi & Ateeq Ur Rehman & Anton Rassõlkin & Maha M. Althobaiti & Habib Hamam & Muhammad Shafiq, 2021. "A Detailed Testing Procedure of Numerical Differential Protection Relay for EHV Auto Transformer," Energies, MDPI, vol. 14(24), pages 1-21, December.
    Full references (including those not matched with items on IDEAS)

    Most related items

    These are the items that most often cite the same works as this one and are cited by the same works as this one.
    1. Seyed Amir Hosseini & Ali Akbar Nazari & Behrooz Taheri & Farzad Razavi & Hamed Hashemi-Dezaki, 2022. "Proposing a New Approach to Generate the Differential Trajectory of the Differential Relays Using COMTRADE Files," Sustainability, MDPI, vol. 14(21), pages 1-25, October.

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:gam:jeners:v:15:y:2022:i:24:p:9603-:d:1007012. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    If CitEc recognized a bibliographic reference but did not link an item in RePEc to it, you can help with this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: MDPI Indexing Manager (email available below). General contact details of provider: https://www.mdpi.com .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.