Evaluation of a Direct Lightning Strike to the 24 kV Distribution Lines in Thailand

Author

Listed:
  • Pornchai Sestasombut

    (Faculty of Engineering, King Mongkut’s Institute of Technology Ladkrabang, Bangkok 10520, Thailand)

  • Atthapol Ngaopitakkul

    (Faculty of Engineering, King Mongkut’s Institute of Technology Ladkrabang, Bangkok 10520, Thailand)

Abstract

This paper evaluates the effect of a lightning strike directly on the 24 kV distribution lines in Thailand, where such strikes are one of the main causes of power outages. The voltage across the insulator, and the arrester energy absorbed due to the lightning, need to be analyzed for different grounding distances of the overhead ground wire, ground resistance, lightning impact positions, and lightning current waveforms. Analysis and simulations are conducted using the Alternative Transients Program/Electromagnetic Transients Program (ATP/EMTP) to find the energy absorbed by the arrester and the voltages across the insulator. The results indicate that when surge arresters are not installed, the voltage across the insulator at the end of the line is approximately 1.4 times that in the middle of the line. In addition, the ground resistance and grounding distance of the overhead ground wire affect the voltage across the insulator if the overhead ground wire is struck. When surge arresters are installed, a shorter grounding distance of the overhead ground wire and a lower ground resistance are not always desirable; this is because they reduce the back-flashover rate and the voltage across the insulator if lightning strikes the overhead ground wire. However, lightning strikes to the phase conductor result in high arrester energy and the possibility that the arrester will fail. Furthermore, the tail time of the lightning waveform is a significant variable when considering the energy absorbed by the arrester, whereas the front time is important for the voltage across the insulator. In case lightning strikes directly on the connected point between the overhead lines and the underground cables, the distribution line system is protected only by the lightning arrester at the connection point. The overvoltage at the connection point is lower than the basic impulse level at 24 kV of 125 kV, but the overvoltage at the end of the cable is still more than 125 kV in case the cable is longer than 400 m. When the distribution line system is protected by the lightning arrester at both the connection point and the end of the cable, it results in overvoltage throughout the cable is lower than the critical flashover of insulation. This method is the best way to reduce the failure rate of underground cables and equipment that are connected to the distribution line system.

Suggested Citation

  • Pornchai Sestasombut & Atthapol Ngaopitakkul, 2019. "Evaluation of a Direct Lightning Strike to the 24 kV Distribution Lines in Thailand," Energies, MDPI, vol. 12(16), pages 1-31, August.
  • Handle: RePEc:gam:jeners:v:12:y:2019:i:16:p:3193-:d:259275
    as

    Download full text from publisher

    File URL: https://www.mdpi.com/1996-1073/12/16/3193/pdf
    Download Restriction: no

    File URL: https://www.mdpi.com/1996-1073/12/16/3193/
    Download Restriction: no
    ---><---

    Citations

    Citations are extracted by the CitEc Project, subscribe to its RSS feed for this item.
    as


    Cited by:

    1. Petar Sarajcev & Dino Lovric & Tonko Garma, 2022. "Statistical Safety Factor in Lightning Performance Analysis of Overhead Distribution Lines," Energies, MDPI, vol. 15(21), pages 1-19, November.
    2. Nur Alia Farina Mohamad Nasir & Mohd Zainal Abidin Ab Kadir & Miszaina Osman & Muhamad Safwan Abd Rahman & Ungku Anisa Ungku Amirulddin & Mohd Solehin Mohd Nasir & Nur Hazirah Zaini & Nik Hakimi Nik A, 2021. "Impact of Earthing System Designs and Soil Characteristics on Tower Footing Impedance and Ground Potential Rise: A Modelling Approach for Sustainable Power Operation," Sustainability, MDPI, vol. 13(15), pages 1-20, July.
    3. Michał Borecki & Maciej Ciuba, 2023. "Testing of Selected Surge Protection Devices in the Context of the Possibility of Ensuring the Reliability of Power Grids," Energies, MDPI, vol. 16(3), pages 1-15, February.

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:gam:jeners:v:12:y:2019:i:16:p:3193-:d:259275. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    We have no bibliographic references for this item. You can help adding them by using this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: MDPI Indexing Manager (email available below). General contact details of provider: https://www.mdpi.com .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.