IDEAS home Printed from https://ideas.repec.org/a/gam/jeners/v17y2024i22p5783-d1524746.html
   My bibliography  Save this article

Transient and Steady-State Evaluation of Distributed Generation in Medium-Voltage Distribution Networks

Author

Listed:
  • Daniel Guillén-López

    (Energy Transition Research Group, Universidad Politécnica Salesiana, Cuenca 010103, Ecuador)

  • Xavier Serrano-Guerrero

    (Energy Transition Research Group, Universidad Politécnica Salesiana, Cuenca 010103, Ecuador)

  • Antonio Barragán-Escandón

    (Energy Transition Research Group, Universidad Politécnica Salesiana, Cuenca 010103, Ecuador)

  • Jean-Michel Clairand

    (Facultad de Ingenería y Ciencias Aplicadas, Universidad de las Américas, Quito 170122, Ecuador)

Abstract

As power generation systems with increasingly higher capacities are interconnected with distribution networks, a pressing need arises for a thorough analysis of their integration and the subsequent impacts on medium-voltage lines. This study conducts a comprehensive evaluation, encompassing both steady-state and transient behaviours, leading to a holistic assessment of a real-world biogas generation system integrated into a medium-voltage network. Although the methodology does not introduce revolutionary concepts, its detailed application on a real feeder under various operating conditions adds practical value to the existing body of knowledge. The methodology explores various aspects, including voltage profiles, load capacity, power losses, short-circuit currents, and protection coordination in steady-state conditions. Additionally, a transient analysis is performed to examine the system’s response under fault conditions. This systematic approach provides a deep understanding of the system’s behaviour across diverse operational scenarios, enriching the field with practical insights. The key contributions of this study include identifying the effects of distributed generation systems (DGSs) on short-circuit currents, protection coordination, and defining voltage levels that briefly exceed the CBEMA quality curve. The benefits of incorporating a generation system into a distribution network are discussed from various technical perspectives. In a peak demand scenario, with a 1.72 MW generation capacity, the phase current experiences a notable reduction of 35.78%. Concurrently, the minimum peak demand voltage increases from 12.62 to 12.83 kV compared to a nominal voltage of 12.7 kV. Furthermore, the contribution of the generation system to the short-circuit current remains minimal, staying below 4% even under the most adverse conditions. However, our findings reveal that voltage levels exceed the upper limit of the CBEMA quality curve briefly during a single-phase fault with generation, which could potentially damage electronic equipment connected to the grid. Nonetheless, the likelihood of encountering a single-phase grounding fault with zero resistance remains low.

Suggested Citation

  • Daniel Guillén-López & Xavier Serrano-Guerrero & Antonio Barragán-Escandón & Jean-Michel Clairand, 2024. "Transient and Steady-State Evaluation of Distributed Generation in Medium-Voltage Distribution Networks," Energies, MDPI, vol. 17(22), pages 1-24, November.
  • Handle: RePEc:gam:jeners:v:17:y:2024:i:22:p:5783-:d:1524746
    as

    Download full text from publisher

    File URL: https://www.mdpi.com/1996-1073/17/22/5783/pdf
    Download Restriction: no

    File URL: https://www.mdpi.com/1996-1073/17/22/5783/
    Download Restriction: no
    ---><---

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:gam:jeners:v:17:y:2024:i:22:p:5783-:d:1524746. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    We have no bibliographic references for this item. You can help adding them by using this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: MDPI Indexing Manager (email available below). General contact details of provider: https://www.mdpi.com .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.